The Problem
The office manager of a small accounting firm in Wangsa Walk Mall, Wangsa Maju, reached out to Masters Aircond Service KL about a persistent bad smell coming from their ceiling cassette airconds. The office has two Daikin FCC60A 2.5HP ceiling cassette units that serve their 800-sqft open-plan workspace.
Staff had been complaining for weeks about a sour, musty odour that intensified every time the airconds started up. Several employees had started getting headaches and allergy symptoms. The office had tried using air fresheners and even placed the units on "fan only" mode — but the smell persisted. A regular servicing 3 months ago hadn't resolved the issue.
Our Assessment
Ceiling cassette units are harder to inspect than wall-mounted models because the entire unit sits within the ceiling void. Our team brought a stepladder and inspection tools to assess both units properly:
- Heavy biofilm buildup on both evaporator coils — a slimy, greenish-black layer of bacteria and mould that standard servicing doesn't remove
- Drain pans were stagnant — standing water mixed with organic debris, the primary source of the sour smell
- Blower wheels caked with grime — reducing airflow and recirculating contaminated air through the office
- Air filters were clean — confirming that the previous servicing only addressed surface-level cleaning
Standard servicing cannot penetrate biofilm on coils. This required a proper chemical wash — using alkaline-based coil cleaner to dissolve the organic buildup, followed by high-pressure rinsing.
Work Timeline
Step 1: Workspace Protection
Laid protective plastic sheets over desks, computers, and flooring beneath both ceiling cassette units. Ceiling cassette chemical washes involve significant water runoff, so thorough protection is essential.
Step 2: Panel & Filter Removal
Removed the decorative ceiling panels and air filters from both units. Detached the drain pans and soaked them in anti-bacterial solution to kill mould and remove biofilm.
Step 3: Chemical Application
Sprayed professional-grade alkaline coil cleaner across all evaporator coil surfaces on both units. Allowed 15 minutes of dwell time to break down the biofilm and mould layers.
Step 4: High-Pressure Rinse
Used a portable pressure washer to flush the chemical solution and dissolved contaminants from the coils. Collected all runoff water using catch trays — the water was dark brown, showing just how much grime had been embedded.
Step 5: Blower Wheel Cleaning
Removed and cleaned both blower wheels with degreaser and brushes. This step is often skipped in basic chemical washes but makes a huge difference in airflow quality.
Step 6: Reassembly & Air Quality Test
Reinstalled drain pans, filters, and ceiling panels. Ran both units for 30 minutes. The sour smell was completely gone — replaced by clean, fresh cold air.
Results
Lessons & Advice
Ceiling cassette units in offices are particularly prone to biofilm and mould because they run 8–12 hours daily in enclosed, occupied spaces. The constant condensation combined with airborne dust and skin cells creates a perfect breeding ground for bacteria. Regular servicing cleans the surface, but a chemical wash every 12–18 months is necessary to address deep-seated contamination.
If your office aircond smells bad even after servicing, it's almost certainly a biofilm problem that needs chemical treatment. Don't ignore it — poor indoor air quality directly affects employee health, productivity, and morale.
For offices running ceiling cassettes daily, we recommend pairing chemical washes with a chemical overhaul every 2–3 years for the deepest possible clean. Masters Aircond Service KL schedules these jobs during weekends or lunch hours to minimise disruption to your business.